SEVERITY AND EXPLOITATION CONTEXT

CVE-2012-6440: Rockwell Automation ControlLogix PLC Improper Input Validation

Review published vectors, EPSS probability and CISA KEV status independently.

Lookup reads saved CVE and CISA snapshots from this site and requests EPSS from FIRST. The CVE source is contacted when a saved record is unavailable or you request a refresh. External providers receive your IP address. Finding notes and saved assessments are not sent by this feature.

Rockwell Automation ControlLogix PLC Improper Input Validation

The Web server password authentication mechanism used by the products is vulnerable to a MitM and Replay attack. Successful exploitation of this vulnerability will allow unauthorized access of the product’s Web server to view and alter product configuration and diagnostics information. Rockwell Automation EtherNet/IP products; 1756-ENBT, 1756-EWEB, 1768-ENBT, and 1768-EWEB communication modules; CompactLogix L32E and L35E controllers; 1788-ENBT FLEXLogix adapter; 1794-AENTR FLEX I/O EtherNet/IP adapter; ControlLogix 18 and earlier; CompactLogix 18 and earlier; GuardLogix 18 and earlier; SoftLogix 18 and earlier; CompactLogix controllers 19 and earlier; SoftLogix controllers 19 and earlier; ControlLogix controllers 20 and earlier; GuardLogix controllers 20 and earlier; and MicroLogix 1100 and 1400

Published CVE snapshot: 2026-10-22. Record last updated: 2026-06-03T13:36:26.519Z. The live panels refresh separately; this snapshot remains available if a source cannot be reached.

View the CVE Program source record

CISA-ADP · CVSS 3.1: 4.8 Medium

Calculated from the published vector. Base score: 4.8. Provider-reported Base score: 4.8.

Vector and metric explanationsCVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:L/I:L/A:N
MetricValueMeaning
Attack vector (AV)NReachable across a network boundary, including internet or routed network paths.
Attack complexity (AC)HSuccessful exploitation depends on conditions beyond the attacker’s control, requiring additional preparation or execution effort.
Privileges required (PR)NThe attacker needs no privileges before exploiting the vulnerability.
User interaction (UI)NNo other user must participate for exploitation to succeed.
Scope (S)UConsequences stay within resources managed by the same security authority.
Confidentiality (C)LSome information is disclosed, with limited scope or seriousness of the direct consequence.
Integrity (I)LSome modification is possible, with limited scope or consequence.
Availability (A)NNo availability impact is demonstrated.

These definitions explain provider selections; they do not independently verify exploitation.

Review vector in calculator

Affected products reported by the provider

  • Rockwell Automation · 1756-ENBT, 1756-EWEB, 1768-ENBT, 1768-EWEB communication modules
  • Rockwell Automation · CompactLogix L32E and L35E controllers
  • Rockwell Automation · 1788-ENBT FLEXLogix adapter
  • Rockwell Automation · 1794-AENTR FLEX I/O EtherNet/IP adapter
  • Rockwell Automation · ControlLogix, CompactLogix, GuardLogix, and SoftLogix
  • Rockwell Automation · CompactLogix and SoftLogix controllers
  • Rockwell Automation · ControlLogix and GuardLogix controllers
  • Rockwell Automation · MicroLogix

Consult the advisory for affected version ranges, configurations and remediation. A product listing alone does not establish that your installation is vulnerable.

Source references (5)

Interpret severity and exploitation separately

CVSS measures technical severity. EPSS estimates exploitation probability over the next 30 days. CISA KEV lists known exploited vulnerabilities. A missing EPSS result is not zero probability, and absence from KEV does not prove no exploitation. Review your deployment and retain the version, vector and evidence when documenting a finding.

Browse CVEs from 2012 · All published CVEs · Calculation methodology