SEVERITY AND EXPLOITATION CONTEXT

CVE-2018-16563: Vulnerability Details

Review published vectors, EPSS probability and CISA KEV status independently.

Lookup reads saved CVE and CISA snapshots from this site and requests EPSS from FIRST. The CVE source is contacted when a saved record is unavailable or you request a refresh. External providers receive your IP address. Finding notes and saved assessments are not sent by this feature.

Vulnerability Details

A vulnerability has been identified in Firmware variant IEC 61850 for EN100 Ethernet module (All versions < V4.35), Firmware variant MODBUS TCP for EN100 Ethernet module (All versions), Firmware variant DNP3 TCP for EN100 Ethernet module (All versions), Firmware variant IEC104 for EN100 Ethernet module (All versions), Firmware variant Profinet IO for EN100 Ethernet module (All versions), SIPROTEC 5 relays with CPU variants CP300 and CP100 and the respective Ethernet communication modules (All versions < V7.82), SIPROTEC 5 relays with CPU variants CP200 and the respective Ethernet communication modules (All versions < V7.58). Specially crafted packets to port 102/tcp could cause a denial-of-service condition in the affected products. A manual restart is required to recover the EN100 module functionality of the affected devices. Successful exploitation requires an attacker with network access to send multiple packets to the affected products or modules. As a precondition the IEC 61850-MMS communication needs to be activated on the affected products or modules. No user interaction or privileges are required to exploit the vulnerability. The vulnerability could allow causing a Denial-of-Service condition of the network functionality of the device, compromising the availability of the system. At the time of advisory publication no public exploitation of this security vulnerability was known.

Published CVE snapshot: 2026-10-22. Record last updated: 2024-08-05T10:24:32.996Z. The live panels refresh separately; this snapshot remains available if a source cannot be reached.

View the CVE Program source record

CVSS scoring availability

No valid CVSS 4.0 or 3.1 vector is available in this snapshot. An older version may appear in the source record. No score has been inferred.

Affected products reported by the provider

  • Siemens · Firmware variant IEC 61850 for EN100 Ethernet module
  • Siemens · Firmware variant MODBUS TCP for EN100 Ethernet module
  • Siemens · Firmware variant DNP3 TCP for EN100 Ethernet module
  • Siemens · Firmware variant IEC104 for EN100 Ethernet module
  • Siemens · Firmware variant Profinet IO for EN100 Ethernet module
  • Siemens · SIPROTEC 5 relays with CPU variants CP300 and CP100 and the respective Ethernet communication modules
  • Siemens · SIPROTEC 5 relays with CPU variants CP200 and the respective Ethernet communication modules

Consult the advisory for affected version ranges, configurations and remediation. A product listing alone does not establish that your installation is vulnerable.

Source references (1)

Interpret severity and exploitation separately

CVSS measures technical severity. EPSS estimates exploitation probability over the next 30 days. CISA KEV lists known exploited vulnerabilities. A missing EPSS result is not zero probability, and absence from KEV does not prove no exploitation. Review your deployment and retain the version, vector and evidence when documenting a finding.

Browse CVEs from 2018 · All published CVEs · Calculation methodology