Vulnerability Details

A vulnerability has been identified in SIMATIC CP 443-1 OPC UA (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V2.7), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (incl. SIPLUS variants) (All versions < V15.1 Upd 4), SIMATIC HMI Comfort Panels 4" - 22" (incl. SIPLUS variants) (All versions < V15.1 Upd 4), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V15.1 Upd 4), SIMATIC IPC DiagMonitor (All versions < V5.1.3), SIMATIC NET PC Software V13 (All versions), SIMATIC NET PC Software V14 (All versions < V14 SP1 Update 14), SIMATIC NET PC Software V15 (All versions), SIMATIC RF188C (All versions < V1.1.0), SIMATIC RF600R family (All versions < V3.2.1), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.5 < V2.6.1), SIMATIC S7-1500 Software Controller (All versions between V2.5 (including) and V2.7 (excluding)), SIMATIC WinCC OA (All versions < V3.15 P018), SIMATIC WinCC Runtime Advanced (All versions < V15.1 Upd 4), SINEC NMS (All versions < V1.0 SP1), SINEMA Server (All versions < V14 SP2), SINUMERIK OPC UA Server (All versions < V2.1), TeleControl Server Basic (All versions < V3.1.1). Specially crafted network packets sent to affected devices on port 4840/tcp could allow an unauthenticated remote attacker to cause a denial of service condition of the OPC communication or crash the device. The security vulnerability could be exploited by an attacker with network access to the affected systems. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise availability of the OPC communication.

Published CVE snapshot: 2026-10-22. Record last updated: 2026-06-03T13:25:38.925Z. The live panels refresh separately; this snapshot remains available if a source cannot be reached.

View the CVE Program source record

CISA-ADP · CVSS 3.1: 7.5 High

Calculated from the published vector. Base score: 7.5. Provider-reported Base score: 7.5.

Vector and metric explanationsCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
MetricValueMeaning
Attack vector (AV)NReachable across a network boundary, including internet or routed network paths.
Attack complexity (AC)LExploitation does not depend on special conditions beyond the attacker’s control.
Privileges required (PR)NThe attacker needs no privileges before exploiting the vulnerability.
User interaction (UI)NNo other user must participate for exploitation to succeed.
Scope (S)UConsequences stay within resources managed by the same security authority.
Confidentiality (C)NNo confidentiality impact is demonstrated.
Integrity (I)NNo integrity impact is demonstrated.
Availability (A)HAvailability is completely lost, or the disruption has a direct, serious consequence.

These definitions explain provider selections; they do not independently verify exploitation.

Review vector in calculator

Affected products reported by the provider

  • Siemens · SIMATIC CP 443-1 OPC UA
  • Siemens · SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants)
  • Siemens · SIMATIC HMI Comfort Outdoor Panels 7" & 15" (incl. SIPLUS variants)
  • Siemens · SIMATIC HMI Comfort Panels 4" - 22" (incl. SIPLUS variants)
  • Siemens · SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 and KTP900F
  • Siemens · SIMATIC IPC DiagMonitor
  • Siemens · SIMATIC NET PC Software V13
  • Siemens · SIMATIC NET PC Software V14
  • Siemens · SIMATIC NET PC Software V15
  • Siemens · SIMATIC RF188C
  • Siemens · SIMATIC RF600R family
  • Siemens · SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants)
  • Siemens · SIMATIC S7-1500 Software Controller
  • Siemens · SIMATIC WinCC OA
  • Siemens · SIMATIC WinCC Runtime Advanced
  • Siemens · SINEC NMS
  • Siemens · SINEMA Server
  • Siemens · SINUMERIK OPC UA Server
  • Siemens · TeleControl Server Basic

Consult the advisory for affected version ranges, configurations and remediation. A product listing alone does not establish that your installation is vulnerable.

Source references (1)

Interpret severity and exploitation separately

CVSS measures technical severity. EPSS estimates exploitation probability over the next 30 days. CISA KEV lists known exploited vulnerabilities. A missing EPSS result is not zero probability, and absence from KEV does not prove no exploitation. Review your deployment and retain the version, vector and evidence when documenting a finding.

Browse CVEs from 2019 · All published CVEs · Calculation methodology