SEVERITY AND EXPLOITATION CONTEXT

CVE-2021-27196: Specially Crafted IEC 61850 Protocol Sequence Vulnerability

Review published vectors, EPSS probability and CISA KEV status independently.

Lookup reads saved CVE and CISA snapshots from this site and requests EPSS from FIRST. The CVE source is contacted when a saved record is unavailable or you request a refresh. External providers receive your IP address. Finding notes and saved assessments are not sent by this feature.

Specially Crafted IEC 61850 Protocol Sequence Vulnerability

Improper Input Validation vulnerability in Hitachi ABB Power Grids Relion 670 Series, Relion 670/650 Series, Relion 670/650/SAM600-IO, Relion 650, REB500, RTU500 Series, FOX615 (TEGO1), MSM, GMS600, PWC600 allows an attacker with access to the IEC 61850 network with knowledge of how to reproduce the attack, as well as the IP addresses of the different IEC 61850 access points (of IEDs/products), to force the device to reboot, which renders the device inoperable for approximately 60 seconds. This vulnerability affects only products with IEC 61850 interfaces. This issue affects: Hitachi ABB Power Grids Relion 670 Series 1.1; 1.2.3 versions prior to 1.2.3.20; 2.0 versions prior to 2.0.0.13; 2.1; 2.2.2 versions prior to 2.2.2.3; 2.2.3 versions prior to 2.2.3.2. Hitachi ABB Power Grids Relion 670/650 Series 2.2.0 versions prior to 2.2.0.13. Hitachi ABB Power Grids Relion 670/650/SAM600-IO 2.2.1 versions prior to 2.2.1.6. Hitachi ABB Power Grids Relion 650 1.1; 1.2; 1.3 versions prior to 1.3.0.7. Hitachi ABB Power Grids REB500 7.3; 7.4; 7.5; 7.6; 8.2; 8.3. Hitachi ABB Power Grids RTU500 Series 7.x version 7.x and prior versions; 8.x version 8.x and prior versions; 9.x version 9.x and prior versions; 10.x version 10.x and prior versions; 11.x version 11.x and prior versions; 12.x version 12.x and prior versions. Hitachi ABB Power Grids FOX615 (TEGO1) R1D02 version R1D02 and prior versions. Hitachi ABB Power Grids MSM 2.1.0 versions prior to 2.1.0. Hitachi ABB Power Grids GMS600 1.3.0 version 1.3.0 and prior versions. Hitachi ABB Power Grids PWC600 1.0 versions prior to 1.0.1.4; 1.1 versions prior to 1.1.0.1.

Published CVE snapshot: 2026-10-22. Record last updated: 2024-09-17T03:17:31.626Z. The live panels refresh separately; this snapshot remains available if a source cannot be reached.

View the CVE Program source record

mitre · CVSS 3.1: 7.5 High

Calculated from the published vector. Base score: 7.5. Provider-reported Base score: 7.5.

Vector and metric explanationsCVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
MetricValueMeaning
Attack vector (AV)NReachable across a network boundary, including internet or routed network paths.
Attack complexity (AC)LExploitation does not depend on special conditions beyond the attacker’s control.
Privileges required (PR)NThe attacker needs no privileges before exploiting the vulnerability.
User interaction (UI)NNo other user must participate for exploitation to succeed.
Scope (S)UConsequences stay within resources managed by the same security authority.
Confidentiality (C)NNo confidentiality impact is demonstrated.
Integrity (I)NNo integrity impact is demonstrated.
Availability (A)HAvailability is completely lost, or the disruption has a direct, serious consequence.

These definitions explain provider selections; they do not independently verify exploitation.

Review vector in calculator

Affected products reported by the provider

  • n/a · n/a

Consult the advisory for affected version ranges, configurations and remediation. A product listing alone does not establish that your installation is vulnerable.

Source references (7)

Interpret severity and exploitation separately

CVSS measures technical severity. EPSS estimates exploitation probability over the next 30 days. CISA KEV lists known exploited vulnerabilities. A missing EPSS result is not zero probability, and absence from KEV does not prove no exploitation. Review your deployment and retain the version, vector and evidence when documenting a finding.

Browse CVEs from 2021 · All published CVEs · Calculation methodology