SEVERITY AND EXPLOITATION CONTEXT

CVE-2023-46280: Vulnerability Details

Review published vectors, EPSS probability and CISA KEV status independently.

Lookup reads saved CVE and CISA snapshots from this site and requests EPSS from FIRST. The CVE source is contacted when a saved record is unavailable or you request a refresh. External providers receive your IP address. Finding notes and saved assessments are not sent by this feature.

Vulnerability Details

A vulnerability has been identified in Security Configuration Tool (SCT) (All versions), SIMATIC Automation Tool (All versions < V5.0 SP2), SIMATIC BATCH V9.1 (All versions < V9.1 SP2 Upd5), SIMATIC NET PC Software V16 (All versions < V16 Update 8), SIMATIC NET PC Software V17 (All versions), SIMATIC NET PC Software V18 (All versions < V18 SP1), SIMATIC NET PC Software V19 (All versions < V19 Update 2), SIMATIC PCS 7 V9.1 (All versions < V9.1 SP2 UC05), SIMATIC PDM V9.2 (All versions < V9.2 SP2 Upd3), SIMATIC Route Control V9.1 (All versions < V9.1 SP2 Upd3), SIMATIC S7-PCT (All versions < V3.5 SP3 Update 6), SIMATIC STEP 7 V5 (All versions < V5.7 SP3), SIMATIC WinCC OA V3.17 (All versions), SIMATIC WinCC OA V3.18 (All versions < V3.18 P025), SIMATIC WinCC OA V3.19 (All versions < V3.19 P010), SIMATIC WinCC Runtime Advanced (All versions < V17 Update 8), SIMATIC WinCC Runtime Professional V16 (All versions < V16 Update 6), SIMATIC WinCC Runtime Professional V17 (All versions < V17 Update 8), SIMATIC WinCC Runtime Professional V18 (All versions < V18 Update 4), SIMATIC WinCC Runtime Professional V19 (All versions < V19 Update 2), SIMATIC WinCC V7.4 (All versions), SIMATIC WinCC V7.5 (All versions < V7.5 SP2 Update 17), SIMATIC WinCC V8.0 (All versions < V8.0 Update 5), SINAMICS Startdrive (All versions < V19 SP1), SINEC NMS (All versions < V3.0), SINUMERIK ONE virtual (All versions < V6.23), SINUMERIK PLC Programming Tool (All versions < V3.3.12), TIA Portal Cloud Connector (All versions < V2.0), Totally Integrated Automation Portal (TIA Portal) V15.1 (All versions), Totally Integrated Automation Portal (TIA Portal) V16 (All versions), Totally Integrated Automation Portal (TIA Portal) V17 (All versions < V17 Update 8), Totally Integrated Automation Portal (TIA Portal) V18 (All versions < V18 Update 4), Totally Integrated Automation Portal (TIA Portal) V19 (All versions < V19 Update 2), SINEC NMS (All versions < V3.0 SP1). The affected applications contain an out of bounds read vulnerability. This could allow an attacker to cause a Blue Screen of Death (BSOD) crash of the underlying Windows kernel.

Published CVE snapshot: 2026-10-22. Record last updated: 2026-06-09T08:46:42.279Z. The live panels refresh separately; this snapshot remains available if a source cannot be reached.

View the CVE Program source record

siemens · CVSS 3.1: 5.9 Medium

Calculated from the published vector. Base score: 6.5. Provider-reported Base score: 6.5.

Vector and metric explanationsCVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:C/C:N/I:N/A:H/E:P/RL:O/RC:C
MetricValueMeaning
Attack vector (AV)LRequires local access, a local execution path, or a user opening an attacker-supplied file.
Attack complexity (AC)LExploitation does not depend on special conditions beyond the attacker’s control.
Privileges required (PR)LThe attacker needs basic user capabilities before exploitation.
User interaction (UI)NNo other user must participate for exploitation to succeed.
Scope (S)CConsequences extend to resources managed by a different security authority.
Confidentiality (C)NNo confidentiality impact is demonstrated.
Integrity (I)NNo integrity impact is demonstrated.
Availability (A)HAvailability is completely lost, or the disruption has a direct, serious consequence.
Exploit code maturity (E)PA proof of concept is available, but substantial modification or expertise is needed for practical use.
Remediation level (RL)OAn official complete fix is available.
Report confidence (RC)CDetailed evidence or authoritative confirmation establishes the vulnerability.

These definitions explain provider selections; they do not independently verify exploitation.

Review vector in calculator

siemens · CVSS 4.0: 8.2 High

Calculated from the published vector. Base score: 8.2. Provider-reported Base score: 8.2.

Vector and metric explanationsCVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:H
MetricValueMeaning
Attack vector (AV)LRequires local access, a local execution path, or a user opening an attacker-supplied file.
Attack complexity (AC)LThere is no specific security-enhancing condition that the attacker must overcome.
Attack requirements (AT)NNo particular deployment or execution prerequisite is needed.
Privileges required (PR)LThe attacker needs basic user capabilities before exploitation.
User interaction (UI)NNo other user must participate for exploitation to succeed.
Confidentiality (VC)NNo confidentiality impact is demonstrated.
Integrity (VI)NNo integrity impact is demonstrated.
Availability (VA)HAvailability is completely lost, or the disruption has a direct, serious consequence.
Confidentiality (SC)NNo impact to this property is established in a subsequent system.
Integrity (SI)NNo impact to this property is established in a subsequent system.
Availability (SA)HHigh impact is established in a system beyond the vulnerable system. Document the affected system and consequence.

These definitions explain provider selections; they do not independently verify exploitation.

Review vector in calculator

Affected products reported by the provider

  • Siemens · Security Configuration Tool (SCT)
  • Siemens · SIMATIC Automation Tool
  • Siemens · SIMATIC BATCH V9.1
  • Siemens · SIMATIC NET PC Software V16
  • Siemens · SIMATIC NET PC Software V17
  • Siemens · SIMATIC NET PC Software V18
  • Siemens · SIMATIC NET PC Software V19
  • Siemens · SIMATIC PCS 7 V9.1
  • Siemens · SIMATIC PDM V9.2
  • Siemens · SIMATIC Route Control V9.1
  • Siemens · SIMATIC S7-PCT
  • Siemens · SIMATIC STEP 7 V5
  • Siemens · SIMATIC WinCC OA V3.17
  • Siemens · SIMATIC WinCC OA V3.18
  • Siemens · SIMATIC WinCC OA V3.19
  • Siemens · SIMATIC WinCC Runtime Advanced
  • Siemens · SIMATIC WinCC Runtime Professional V16
  • Siemens · SIMATIC WinCC Runtime Professional V17
  • Siemens · SIMATIC WinCC Runtime Professional V18
  • Siemens · SIMATIC WinCC Runtime Professional V19
  • Siemens · SIMATIC WinCC V7.4
  • Siemens · SIMATIC WinCC V7.5
  • Siemens · SIMATIC WinCC V8.0
  • Siemens · SINAMICS Startdrive
  • Siemens · SINEC NMS
  • Siemens · SINUMERIK ONE virtual
  • Siemens · SINUMERIK PLC Programming Tool
  • Siemens · TIA Portal Cloud Connector
  • Siemens · Totally Integrated Automation Portal (TIA Portal) V15.1
  • Siemens · Totally Integrated Automation Portal (TIA Portal) V16
  • Siemens · Totally Integrated Automation Portal (TIA Portal) V17
  • Siemens · Totally Integrated Automation Portal (TIA Portal) V18
  • Siemens · Totally Integrated Automation Portal (TIA Portal) V19
  • Siemens · SINEC NMS

Consult the advisory for affected version ranges, configurations and remediation. A product listing alone does not establish that your installation is vulnerable.

Source references (3)

Interpret severity and exploitation separately

CVSS measures technical severity. EPSS estimates exploitation probability over the next 30 days. CISA KEV lists known exploited vulnerabilities. A missing EPSS result is not zero probability, and absence from KEV does not prove no exploitation. Review your deployment and retain the version, vector and evidence when documenting a finding.

Browse CVEs from 2023 · All published CVEs · Calculation methodology